Table of Contents Table of Contents
Previous Page  94 / 210 Next Page
Basic version Information
Show Menu
Previous Page 94 / 210 Next Page
Page Background

BEAM P

LUS

I

NTERIORS

C

OMMERCIAL

, R

ETAIL

A

ND

I

NSTITUTIONAL

W

ATER

U

SE

(WU)

WU 1 W

ATER

Q

UALITY

S

URVEY

Copyright © BEAM Society Limited. All rights reserved. Page 93

6 W

ATER

U

SE

WU1 W

ATER

Q

UALITY

S

URVEY

E

XCLUSION

None

O

BJECTIVE

Ensure that the quality of potable water is satisfactory.

C

REDIT ATTAINABLE

1

C

REDIT

R

EQUIREMENT

1 credit for demonstrating that the quality of potable water meets the

referenced drinking water quality standards at all points of use.

A

SSESSMENT

Criteria

Potable water sampling should be systematic, such as described in

ISO 5667 [

1

]. Sample(s) shall be taken at the farthest point(s) of use

in the distribution system within the project space from the storage

tank of the host building. If water sample(s) can comply with the

seven (7) parameters including pH, colour, turbidity, conductivity, iron,

E.Coli and total coliform as stipulated in the Quality Water

Recognition Scheme for Buildings [

2

] administered by the Water

Supplies Department, the credit can be achieved.

Alternative:

Where the water service installation is not provided in th

e project space ,

the credit can still be attained provided that the Applicant can

demonstrate:

i.

host building is already awarded with at least Blue Certificate

under the Quality Water Recognition Scheme issued by

Water Supplies Department for potable and flushing water

or

ii.

twin-tank system is installed in the host building for potable

water;

Documentation

Credit shall be achieved when the Applicant provides the

documentation stated below, to demonstrate compliance:

i.

summary table:

ii.

drawings, with plumbing schematic, layout drawings;

iii.

Laboratory test report(s) including details of the analysis of

sample(s) taken from potable water outlets used to supply for

human consumption.

Alternative I:

i.

Certificate(s) for host building;

ii.

Record photographs;

Alternative II:

i.

drawings, schematic for twin tank system;

1

ISO 5667-5:2006 Water quality -- Sampling -- Part 5: Guidance on sampling of drinking water from treatment works

and piped distribution systems

2

Water Supplies Department. Quality Water Recognition Scheme for Buildings

http://www.wsd.gov.hk/en/customer_services_and_water_bills/application_for_licence_certificate/quality_water_reco gnition_scheme_for_buildings/index.html