9.2.1 Commissioning Plan
9.2.2 Commissioning Reports
9.2.3 Operations and Maintenance Manual
9.2.4 Energy Management Manual
9.2.1 C
OMMISSIONING
P
LAN
To execute commissioning in a comprehensive and orderly manner a
commissioning plan, covering every system, equipment, and
component shall be prepared. The plan shall include:
i.
start-up and inspection checklists and procedures;
ii.
functional performance testing procedures and checklists;
iii.
testing, adjusting, and balancing;
iv.
development of an operations and maintenance manual and
energy management manual;
v.
completion of the commissioning report;
For each system commissioned the plan shall provide:
i.
an overview of the tasks to be executed during
commissioning;
ii.
a list of all features to be commissioned;
iii.
a list of reference documents related to commissioning,
including specification references, drawing list, and submittal
drawings;
iv.
a list of primary participants in the commissioning process and
their responsibilities;
v.
a plan for management, communication and documentation;
vi.
description of checklists and tests to be performed, with
reference to specification;
vii.
pre-start and start-up checklists;
viii.
list of the functional performance tests to be performed;
ix.
description of the training to be provided to the operations and
maintenance personnel
9.2.2 C
OMMISSIONING
R
EPORT
The commissioning report shall document the commissioning process,
and results, it shall comprise:
i.
executive summary;
ii.
list of participants and their respective roles;
iii.
brief project space description;
iv.
an overview of the scope of testing and commissioning;
v.
general description of testing and verification methods;
vi.
list of each feature component, and system commissioned;
vii.
for each piece of commissioned equipment, the determination
of the iCxA regarding the adequacy of the equipment,
documentation and training.
The commissioning report shall address the following areas:
i.
adequacy of equipment with respect to construction
documents and design intent;
ii.
equipment installation;