9.3 A

SSUMPTIONS AND

B

ASELINES FOR

W

ATER

C

ONSUMPTION

Copyright © BEAM Society Limited. All rights reserved. Page 139

The calculation shall list each type of water using device all data used shall reference the source. It

shall include water taps for basin, pantry, kitchen, bath and shower heads but exclude water closet,

urinal, water features, appliance and irrigation. There should be separate entries for water use in

male and female facilities. The water saving calculation format shall be as follows:

Device (Reference

catalogue

(A)

)

Duration of

each

operation

(seconds)

Daily

number of

uses per

occupant

Rated flow rate

(litres/minute)

Estimated daily

consumption per

occupant (litres)

Baseline (c)

As-built

Baseline (c)

As-built

Tap Toilet (Model

123)

10

5

6

4

5

3.3

Tap Pantry (Model

456)

15

1

8

4.5

2

1.1

Estimated total daily consumption per occupant (litres)

7

4.4

Number of occupants

(B)

30

Number of day

365

Estimated total annual consumption (litres)

76,650

48,180

% of water saving:

37.1%

Notes:

(A) Reference catalogues or manufacturer specification should show device type, model

number, flow rate and WELS label (if provided) as substantiation to the information filled in

the calculation, where important information in the reference catalogues or manufacturer

specification shall be highlighted or circled for easy identification.

(B) The number of occupants shall be taken from the design brief or OPR. If this data is not

obtainable then, in the absence of any other data, the occupant space allowance should be

reference to the Occupancy Considerations as shown above.

(C) The baseline data shall utilize the appropriate flow rate data listed in the table below.

The baseline water flow rate data used in calculations shall use the following data:

description

size (mm)

flow rate

unit

shower head

9.5 l/min

kitchen sink pillar tap (pantry)

22

6 l/min

kitchen sink mixer tap (pantry)

22

6 l/min

pillar tap

15

6 l/min

mixer tap

15

9 l/min

bath pillar tap

22

15 l/min

bath mixer tap

22

15 l/min

bidet

15

5 l/min

Pre-rinse spray valves kitchen

15

7 l/min

WC

7 L/flush

WC hose spray

15

5 l/min

Urinal

15

4.5 L/flush

Washing machine (horz)

15

12.6 L/kg/cycle

Washing machine (vert)

15

22 L/kg/cycle