Table of Contents Table of Contents
Previous Page  177 / 188 Next Page
Basic version Information
Show Menu
Previous Page 177 / 188 Next Page
Page Background

BEAM P

LUS FOR

E

XISTING

B

UILDINGS

A

PPENDICES

V

ERSION

1.2

8.1 A

NNUAL

E

NERGY

U

SE

Copyright © 2012 BEAM Society Limited. All rights reserved.

A - 7

items listed in Table 8.1 in Section 8 (from Code of Practice for

Energy Efficiency of Building Services Installation – 2012 Edition [2]);

Where applicable, those requirements listed in Table 9.4 of Code of

Practice for Energy Efficiency of Building Services Installation – 2012

Edition shall be strictly complied with as a pre-requisite for credits under

the Performance-based Approach. Substitutes or trade-offs in

performance for such requirements are not accepted.

Items covered in the referenced codes not defined here as basic

requirements are regarded as the minimum (benchmark) performance

for the relevant systems or components, but trade-off in performance of

such systems or components with other systems or components is

allowed within the overall energy performance assessment.

Other building specific requirements are given in relevant sections that

define the assessment method for the particular building type.

T

ABLE

8.1

BASIC REQUIREMENTS GIVEN IN

B

UILDING

E

NERGY

C

ODE

Basic Requirements for Performance-based Approach in the Code of Practice for

Energy Efficiency of Building Services Installation – 2012 Edition

Lighting installations, given in Section 5 of BEC

-

Lighting control

(1)

(clause no. 5.5 )

(2)

Air-conditioning installations, given in Section 6 of BEC

-

System load calculation (clause no. 6.4 )

(2)

-

Separate air distribution system for process zone (clause no. 6.5 )

(2)

-

Air distribution ductwork leakage limit (clause no. 6.6 )

(2)

-

Pumping system variable flow (clause no. 6.8 )

(2)

-

Frictional loss of water piping system (clause no. 6.9 )

(2)

-

System control (clause no. 6.10 )

(2)

-

Thermal insulation (clause no. 6.11 )

(2)

-

Energy metering (clause no. 6.13 )

(2)

Electrical installations, given in Section 7 of BEC

-

Power distribution (clause no. 7.4 )

(2)

-

Motor installation (clause no. 7.5 )

(2)

-

Power quality (clause no. 7.6 )

(2)

-

Metering and monitoring facilities (clause no. 7.7 )

(2)

Lift and escalator installations, given in Section 8 of BEC

-

Electrical power (clause no. 8.4 )

(2)

-

Utilization of power (clause no. 8.5 )

(2)

-

Total harmonic distortion (clause no. 8.6 )

(2)

-

Metering and monitoring facilities (clause no. 8.7 )

(2)

Energy efficiency requirements on building envelope

-

Overall thermal transfer value, requirements same as given in Building (Energy Efficiency)

Regulation (Cap. 123M)

(1) For multi-tenanted buildings, this shall be confirmed by submitting a “Tenant’s fitting out specification” that governs

lighting installations and controls inside tenants’ areas.

(2) Clause number in BEC

8.1.4 S

IMULATION

R

EQUIREMENTS

The computer simulation requirements shall be referred to Section A2 -

Numerical Method for Building Energy Analysis in BEC.

Clause A2.1 in BEC states: The numerical method for the building

energy analysis should be targeted for the estimation of energy

consumption in buildings in a comprehensive manner and should include

calculation methodologies for the building components or systems being

considered.

The required numerical method should include but not limit to the

2

Electrical and Mechanical Services Department. Code of Practice for Energy Efficiency of Building Services Installation

http://www.emsd.gov.hk/emsd/e_download/pee/BEC_2012.pdf