8.1 A
NNUAL
E
NERGY
U
SE
Copyright © 2012 BEAM Society Limited. All rights reserved.
A - 4
assumed same for existing building and assessed building. For the
purpose of quantifying energy reduction as a result of efficient design
towards demonstration of compliance to this credit, the acceptable
reduction measures can be:
(a) An improvement over the corresponding minimum allowable levels
of performance in any one or more of the items listed with energy
efficiency requirements in Section 5 to 8 of BEC (such as lighting
A/C, vertical transport and electrical)
(b) Having recovered energy or renewable energy captured or
generated on site
(c) Adoption of load reduction strategies, such as (but not limited to)
natural ventilation, free-cooling, natural daylight etc. When the
selected simulation program cannot adequately model a design or a
control strategy, exceptional calculation method can be used with
reference to 8.1.4 - ASHRAE Approach (see below)
(d) Addition of energy reduction components, such as (but not limited to)
variable speed drives, heat recovery, energy efficient lamps and
ballasts, smart control over lift banks etc), light pipes and light tubes,
sensors (daylight, CO
2
occupancy), dimming devices. (see below)
(e) Reduction in equipment/process loads, where sufficient evidence is
given to support the savings over common practices
(f) Reduction in energy use through the selection of a more efficient
baseline cooling system. (See below)
Baseline Building Design (Reference Building)
A3.3.1 in the BEC states that “the simulation model of the reference
building should be developed by modifying the model of the designed
building as described in clause A3.2 (simulation of the designed
building). Except as specifically instructed in the Appendix of the BEC, all
building systems and equipment should be modeled identically for both
the reference building and designed building.”
For the purpose of assessment of this credit, the baseline building should
also be developed based on designed building but with the following
important distinctions:
(a) Modifications as described by clauses A3.3.2, A3.3.4, A3.3.6, and
A3.3.7
(b) Energy saving devices and load reduction strategies need not be
included in the baseline building. These are defined as components
or operation strategies that reduce energy use while delivering the
same level of environmental comfort to the building. Classification of
energy saving devices and load reduction strategies is subject to the
acceptance of the BEAM assessor.
Baseline Air-Conditioning System
In A3.3.5 of BEC, concerning air-conditioning system:
“The air-conditioning systems, zoning and equipment types of the
reference building should be identical to the designed building; and the
system and equipment of the reference building should exactly meet the
relevant requirements in Section 6 of the BEC.”
For the purpose of assessment of this credit, the baseline air-
conditioning should have identical zoning to the designed building, but
should be modeled with a system and equipment as described in the
following table: