Premises where air-conditioning is provided by window units or split

units.

O

BJECTIVE

Ensure that the air-conditioning system can provide the stated design

conditions in occupied spaces under changing load conditions.

C

REDITS ATTAINABLE

2

P

REREQUISITES

None.

C

REDIT REQUIREMENT

a) Temperature

1 credit for sustaining the air temperature at the design value within

±1.5

C when the air side system is operating at steady state under

normal occupied periods.

b) Room air distribution

1 credit where room air diffusers satisfy the Air Diffusion Performance

Index.

A

SSESSMENT

The Client shall provide evidence in the form of a report prepared by a

suitably qualified person detailing the performance criteria with respect to

thermal comfort conditions for all types of premises included in the

building, and the results of the measurements in the specified sample of

premises.

a) Temperature

The measurement locations shall include at least one representative

sample of each type of premises (occupied spaces) as defined by the

type of HVAC system used, design occupancy density, nature of usage,

zoning, etc. The main physical parameters of the indoor climate (air

temperature and relative humidity) are undertaken in normal occupied

periods. The results shall demonstrate compliance with the prescribed

design criteria within the prescribed limits, for a minimum of 90% of the

prescribed locations. The measurement shall be made with reference to

the current EPD’s IAQ certification scheme. The sensors used in the

measurement survey shall have an accuracy that complies with

ASHRAE 55-1992 [1], ISO 7726 [2] or equivalent.

Where certification under the IAQ Certification scheme [3] is current and

covers all parts of the building for which BEAM certification is being

sought then the credit shall be awarded.

b) Room air distribution

The measurement locations shall be as for a). It is acceptable to

demonstrate the credit compliance by either calculation or by in-situ

measurement.

B

ACKGROUND

The HVAC system should be able to maintain room conditions (within

acceptable tolerances) under normal occupied periods. Measurements

under such circumstances can demonstrate compliance with the

operating requirements.

1

American Society of Heating, Refrigeration and Air-conditioning Engineers. ASHRAE 55-1992: Thermal Environmental

Conditions for Human Occupancy. Atlanta 1992.

2

International Standard Organization. International standard 7726, Ergonomics of the thermal environment — Instruments

for measuring physical quantities. 1998.

3

Indoor Air Quality Management Group. A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places.

http://www.iaq.gov.hk/cert/doc/CertGuide-eng.pdf