Table of Contents Table of Contents
Previous Page  146 / 188 Next Page
Basic version Information
Show Menu
Previous Page 146 / 188 Next Page
Page Background

BEAM P

LUS FOR

E

XISTING

B

UILDINGS

I

NDOOR

E

NVIRONMENTAL

Q

UALITY

(I

EQ

)

V

ERSION

1.2

I

EQ

12 L

OCALISED

V

ENTILATION

Copyright © 2012 BEAM Society Limited. All rights reserved.

Page 128

6

IEQ

6.4

V

ENTILATION

I

EQ

12 L

OCALISED

V

ENTILATION

E

XCLUSIONS

None.

O

BJECTIVE

Prevent exposure of building occupants to concentrated indoor sources

of pollutants.

C

REDITS ATTAINABLE

1

P

REREQUISITES

Compliance with CAP 123J Building (Ventilating Systems) Regulations.

C

REDIT REQUIREMENT

1 credit for the provision of an adequate ventilation system for

rooms/areas where significant indoor pollution sources are generated.

A

SSESSMENT

The Client shall provide evidence in the form of a report prepared by a

suitably qualified person detailing the design criteria that have been

adopted and details of the ventilation system providing for local exhaust

where concentrated pollutant sources are likely to be present. The report

shall provide details of tests and the results demonstrating that the

design performance is achieved. Where the design ventilation rate

specified is lower than that specified in a recognised international or

national standard the client shall demonstrate through appropriate testing

that there is 99% isolation between areas with concentrated pollutant

sources and occupied areas.

B

ACKGROUND

Concentrated pollution sources are best managed at source. The

provision of localised ventilation, segregated from the general ventilation,

is an appropriate strategy. In commercial and similar premises sources

such as photocopying equipment, smoking lounges, etc. should be

provided with dedicated exhaust systems. In other buildings local

exhaust is intended to remove contaminants from specific rooms such as

kitchens, in which concentrated sources are expected.

D

OMESTIC

K

ITCHENS

PNAP No. APP-130 [1] specifies performance based criteria for kitchen

ventilation as an alternative means of satisfying Building (Planning)

Regulations (B(P)Reg.) 30, 31 and 32. These criteria are 1.5 Ach under

natural ventilation, plus 5 Ach from mechanical means i.e. these values

are by definition the minimum legal requirement. Whilst these are

performance based alternatives to the prescriptive criteria they are

considered worthy of credit. It should be noted that specifying higher

values may result in negatively pressurizing the building and causing

other IAQ problems with in flow of air from other spaces.

Elsewhere, ASHRAE 62.2 [2] states that kitchen fans are mandatory as

this standard considers that windows do not provide sufficient ventilation,

although this standard specifically applies to low rise residential units (3

storeys or less above grade) and wind conditions may not be as

favourable for ventilation as in the case of high rise buildings. The basic

requirement is that a vented cooker hood can exhaust 100 cfm (approx

50 l/s). An alternative approach is that ventilation (either continuous or

intermittent) of 5 Ach be achieved.

1

Buildings Department. Practice Note for Authorized Persons, Registered Structural Engineers and Registered

Geotechnical Engineers, PNAP No. APP-130 Lighting and Ventilation Requirements - Performance Based Approach.

http://www.bd.gov.hk/english/documents/pnap/APP/APP130.pdf

2

ASHRAE 62.2-2003. Ventilation and Acceptable Indoor Air Quality in Low Rise Residential Buildings. American Society of

Heating, Refrigerating and Air Conditioning Engineers. Atlanta. 2003.