Figure 8.1

Building energy performance assessment

8.1.3 K

EY

F

EATURES

The key features of the Performance-based Approach are as follows.

the ‘Energy Budget’ for an ASSESSED BUILDING is the predicted

Annual Energy Use for a BASELINE BUILDING (zero-credit

benchmark);

the BASELINE BUILDING model has the same shape and

dimensions, comprises the same mix of areas and types of premises

as the ASSESSED BUILDING (except for window-to-wall ratio

adjustment to meet the relevant regulatory requirement);

the BASELINE BUILDING model will incorporate a range of standard

(default) characteristics such that the model represents a building

whose energy performance barely meets the relevant regulatory

requirements or meets only ‘basic’ design quality ;

as far as possible the predicted Annual Energy Use of the

ASSESSED BUILDING will be based on its specific design

characteristics (except for some parameters for which default values

are specified - see Section 8.2); and

the number of credits awarded is determined by the percentage

reduction in the predicted Annual Energy Use or Annual CO

2

Emissions of the ASSESSED BUILDING relative to the BASELINE

BUILDING.

(SIMULATION)

SHAPE AND DIMENSIONS, MIX OF AREAS

AND TYPES OF PREMISES SAME AS

ASSESSED BUILDING

DEFAULTS CHARACTERISTICS:

BARELY MEET MINIMUM PERFORMANCE

CRITERIA IN CODES/STANDARDS OR

‘BASIC’

PREDICTED ENERGY USE AND PEAK

ELECTRICITY DEMAND

(A/C ENERGY + LIGHTING + EQUIPMENT

ENERGY)

ASSESSMENT OF ANNUAL ENERGY USE AND PEAK ELECTRICITY

DEMAND

ZERO-CREDIT BENCHMARKS FOR

ANNUAL ENERGY USE

AND

PEAK ELECTRICITY DEMAND

ASSESSED BUILDING

(SIMULATION)

SHAPE AND DIMENSIONS

ORIENTATION

ENVELOPE

MIX OF AREAS

TYPES OF SYSTEMS

--

SPECIFIC DESIGN

DESIGN ENHANCEMENTS NOT

INCLUDED IN BASELINE BUILDING

SIMULATION

+

APPLICABLE DEFAULTS

PREDICTED ANNUAL ENERGY USE

AND PEAK ELECTRICITY DEMAND

PERCENTAGE REDUCTION IN ANNUAL ENERGY USE

AND PEAK ELECTRICITY DEMAND (WHERE APPLICABLE)

ANNUAL ENERGY USE CREDITS

PEAK DEMAND CREDITS

AWARDED FOR THE ASSESSED BUILDING

ENERGY BUDGET FOR ASSESSED

BUILDING