relevant requirements in Section 6 of the BEC.”

For the purpose of assessment of this credit, the baseline air-

conditioning shall have identical zoning to the designed building, but

shall be modeled with a system and equipment as described in the

following table:

Public Housing Private

Housing

Industrial,

commercial,

and other

building types

< CFA

14,000sqm

Industrial,

commercial,

and other

building

types > CFA

14,000sqm

Cooling

Generation

Unitary air-

conditioner,

non-split-type

Unitary air-

conditioner,

split-type

Unitary air-

conditioner,

split-type

Chiller*

Terminal type

N/A

N/A

N/A

VAV

Heat Rejection Air-cooled

Air-cooled

Air-cooled

Water-cooled

Reference shall be made to the latest BEC on the performance of

individual components of the systems.

*For buildings with area less than 20,000 sqm – 2 water-cooled screw

chillers sized equally, for buildings with area more than 20,000 sqm – 2

water cooled centrifugal chillers minimum with chillers added so that no

chiller is larger than 2800 kW, all sized equally.

Baseline Envelope Design

Also, in A3.3.2 (d) of BEC, concerning building envelope:

“For buildings not governed by the OTTV requirements, the dimensions

of the windows, doors and skylights shall be the same as the designed

building”

Again, for the purpose of the assessment of this credit, in the case of

buildings not governed by the OTTV requirements, the baseline building

envelope need not be the same as the designed building, instead

suggested baseline envelope specifications are given in Appendix 8.2.