Table of Contents Table of Contents
Previous Page  38-39 / 188 Next Page
Basic version Information
Show Menu
Previous Page 38-39 / 188 Next Page
Page Background

BEAM P

LUS FOR

E

XISTING

B

UILDINGS

F

RAMEWORK

V

ERSION

1.2

Copyright © 2012 BEAM Society Limited. All rights reserved.

Page 22

I

EQ

15 T

HERMAL

C

OMFORT IN

N

ATURALLY

V

ENTILATED

P

REMISES

1 credit for demonstrating indoor operative temperatures in occupied/habitable

rooms meet the 80% acceptability limits.

Alternately,

1 credit for demonstrating the Predicted Mean Vote (PMV) in

occupied/habitable rooms is between –1 and +1.

Buildings that are not

designed to utilize

natural ventilation.

1

1 credit for sustaining the air temperature at the design value within ±1.5

C when

the air-conditioning unit is operating at steady state under normal occupied

periods.

1

I

EQ

16 N

ATURAL

L

IGHTING

1 credit where at least 80% of the floor area in all normally occupied spaces is

adequately lit with an average daylight factor of 1%.

2 credits where at least 95% of the floor area in all normally occupied spaces is

adequately lit with an average daylight factor of 1%.

None.

2

I

EQ

17 I

NTERIOR

L

IGHTING IN

N

ORMALLY

O

CCUPIED

A

REAS

1 credit where the prescribed lighting performance in each type of premises in

respect of illuminance and lighting quality is achieved.

It is required to fulfill prescribed lighting performance in respect of maintained

illuminance and illuminance variation; and the limiting unified glare rating is

achieved and light sources have an appropriate colour rendering index.

Residential buildings,

hotels and apartment

buildings.

1

1 BONUS credit for providing automatic control of artificial lighting

such as daylight sensors at perimeter zone and/or occupancy sensor.

1B

I

EQ

18 I

NTERIOR

L

IGHTING IN

A

REAS NOT

N

ORMALLY

O

CCUPIED

1 credit where the prescribed lighting performance in each type of common or

service space in respect of light output and lighting quality is achieved.

None.

1

I

EQ

19 R

OOM

A

COUSTICS

1 credit for demonstrating that internal noise levels are within the prescribed

criteria and the mid-frequency reverberation time in applicable rooms meets the

prescribed criteria for give types of premises.

Based on the nature of the building, relaxation should be allowed in considering

the acceptance of this credit. The applicant should provide full submission of the

design and calculation to justify the relaxation.

Buildings/premises

where speech

intelligibility is not

important, and rooms of

a special acoustical

nature.

1