BEAM P
LUS FOR
E
XISTING
B
UILDINGS
E
NERGY
U
SE
(E
U
)
V
ERSION
1.2
E
U
1 R
EDUCTION OF
CO
2
E
MISSIONS
Copyright © 2012 BEAM Society Limited. All rights reserved.
Page 69
4
E
NERGY
U
SE
4.1
A
NNUAL
E
NERGY
U
SE
E
U
1 R
EDUCTION OF
CO
2
E
MISSIONS
E
XCLUSIONS
None
O
BJECTIVE
Reduce the consumption of non-renewable energy resources and the
consequent harmful emissions of Carbon dioxide (CO
2
) to the
atmosphere.
C
REDITS ATTAINABLE
15
P
REREQUISITES
Eu P1 Minimum Energy Performance
C
REDIT REQUIREMENT
a) Commercial and Hotel Buildings,
1 to 15 credits for a reduction of CO
2
emissions or annual energy
consumption by:
3%, 5%, 7%, 9%, 11%, 14%, 17%, 20%, 23%, 26%, 29%, 33%, 37%,
41% and 45% respectively.
b) Educational Buildings,
1 to 15 credits for reduction of CO
2
emissions or annual energy
consumption by:
3%, 4%, 5%, 6%, 7%, 9%, 11%, 13%, 15%, 17%, 19%, 21%, 24%, 27%
and 30% respectively.
c) Residential Buildings,
1 to 15 credits for reduction of CO
2
emissions or annual energy
consumption by:
3%, 4%, 5%, 6%, 7%, 8%, 9%, 10%, 11%, 12%, 13%, 14%, 16%,18%
and 20% respectively.
d) For other Building Types,
1 to 15 credits for reduction of CO
2
emissions or annual energy
consumption by:
1%, 2%, 3%, 4%, 5%, 6%, 7%, 8%, 9%, 10%, 12%, 14%, 16%,18% and
20% respectively.
A
LTERNATIVE
C
REDIT
R
EQUIREMENT
1 credit for compliance with the Code of Practice for Energy Efficiency of
Air Conditioning Installations.
1 credit for compliance with the Code of Practice for Energy Efficiency of
Lighting Installations.
and energy use in comparison with similar premises:
1 credit where annual energy use is ≤ 40% cumulative percentage.
2 credits where annual energy use is ≤ 30% cumulative percentage.
3 credits where annual energy use is ≤ 20% cumulative percentage.
4 credits where annual energy use is ≤ 10% cumulative percentage.
or, energy use reductions as demonstrated by billing/metering data:
1 credit where the reduction in annual energy use has been 10%.
2 credits where the reduction in annual energy use has been 15%.
3 credits where the reduction in annual energy use has been 20%.
A
SSESSMENT
The number of credits awarded will be determined with reference to the
percentage reduction of CO
2
emissions or annual energy consumption of
the Assessed Building relative to the benchmark (zero-credit) criteria
evaluated from an equivalent Baseline Building model (see Section 8.1).
The calculation shall be done in terms of units of either CO
2
– kg or kWh
per year. A simple conversion factor shall be adopted with reference to