BJECTIVE

Reduce the consumption of non-renewable energy resources and the

consequent harmful emissions of Carbon dioxide (CO

2

) to the

atmosphere.

C

REDITS ATTAINABLE

15

P

REREQUISITES

Eu P1 Minimum Energy Performance

C

REDIT REQUIREMENT

a) Commercial and Hotel Buildings,

1 to 15 credits for a reduction of CO

2

emissions or annual energy

consumption by:

3%, 5%, 7%, 9%, 11%, 14%, 17%, 20%, 23%, 26%, 29%, 33%, 37%,

41% and 45% respectively.

b) Educational Buildings,

1 to 15 credits for reduction of CO

2

emissions or annual energy

consumption by:

3%, 4%, 5%, 6%, 7%, 9%, 11%, 13%, 15%, 17%, 19%, 21%, 24%, 27%

and 30% respectively.

c) Residential Buildings,

1 to 15 credits for reduction of CO

2

emissions or annual energy

consumption by:

3%, 4%, 5%, 6%, 7%, 8%, 9%, 10%, 11%, 12%, 13%, 14%, 16%,18%

and 20% respectively.

d) For other Building Types,

1 to 15 credits for reduction of CO

2

emissions or annual energy

consumption by:

1%, 2%, 3%, 4%, 5%, 6%, 7%, 8%, 9%, 10%, 12%, 14%, 16%,18% and

20% respectively.

A

LTERNATIVE

C

REDIT

R

EQUIREMENT

1 credit for compliance with the Code of Practice for Energy Efficiency of

Air Conditioning Installations.

1 credit for compliance with the Code of Practice for Energy Efficiency of

Lighting Installations.

and energy use in comparison with similar premises:

1 credit where annual energy use is ≤ 40% cumulative percentage.

2 credits where annual energy use is ≤ 30% cumulative percentage.

3 credits where annual energy use is ≤ 20% cumulative percentage.

4 credits where annual energy use is ≤ 10% cumulative percentage.

or, energy use reductions as demonstrated by billing/metering data:

1 credit where the reduction in annual energy use has been 10%.

2 credits where the reduction in annual energy use has been 15%.

3 credits where the reduction in annual energy use has been 20%.

A

SSESSMENT

The number of credits awarded will be determined with reference to the

percentage reduction of CO

2

emissions or annual energy consumption of

the Assessed Building relative to the benchmark (zero-credit) criteria

evaluated from an equivalent Baseline Building model (see Section 8.1).

The calculation shall be done in terms of units of either CO

2

– kg or kWh

per year. A simple conversion factor shall be adopted with reference to