Background ventilation is a combination of uncontrolled air infiltration and

ventilation through purposely designed vents. Purpose designed

ventilation is preferable to relying on uncontrolled infiltration. BEAM

encourages designs that provide for adequate background ventilation by

natural means.

Background ventilation is intended to dilute the unavoidable contaminant

emissions from people and materials (e.g. radon) and for control of

internal moisture levels due to occupant activities in order to minimise

risk of mould growth. During periods when windows and other openings

are closed it is possible for indoor radon levels to rise above the criteria

recommended by the Environmental Protection Department [6]. Local

research on residential buildings suggests that 0.5 to 1 ACH would be

sufficient to maintain radon below the target level.

For domestic buildings the Building Authority (BA) is prepared to accept

the following alternative performance standards on the provision of

natural ventilation in habitable rooms [7]:

Room of domestic

building

Air Change per Hour (ACH)

Habitable Room

1.5 (natural means)

Kitchen

1.5 (natural means) plus 5 (mechanical

means)

6

Indoor Air Quality Management Group. A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places.

http://www.iaq.gov.hk/cert/doc/CertGuide-eng.pdf

7

Buildings Department. Practice Note for Authorized Persons, Registered Structural Engineers and Registered

Geotechnical Engineers, PNAP No. APP-130 Lighting and Ventilation Requirements – Performance-based Approach.

http://www.bd.gov.hk/english/documents/pnap/APP/APP130.pdf