BEAM Plus Interiors

Commercial, Retail and Institutional

Submission Template for IEQ 5

Tenant Exhaust

Copyright © 2013 BEAM Society Limited. All rights reserved.

Page 1 of 1

Credit Requirements:

1 credit for independent local exhaust system(s) for all photocopy / printing rooms

and other areas** indoor pollution is generated.

Credit Attainable:

1

Credit anticipated for this submission:

Enclosure

Drawings, architectural, location, floor area, for pollutant sources (photocopy / printing rooms);

Drawings, engineering schematic, sections, layout indicating ductwork/fan exhaust system(s);

Drawings, engineering ductwork scale 1:50 indicating distance between exhaust and intake positions;

Records, T&C records with exhaust fan schedule, and controls;

Records, T&C record for exhaust rate of 2.5l/s/sqm, control panel, and power consumption;

Manufacturer’s catalogue, technical data sheet for exhaust fan(s);

Record Photographs, for site work, ductwork, fan, wiring, exhaust discharge point, and completed installation

** Commercial Kitchens are excluded