IEQ 5 T

ENANT

E

XHAUST

Copyright © BEAM Society Limited. All rights reserved. Page 108

IEQ 5 T

ENANT

E

XHAUST

E

XCLUSION

None.

O

BJECTIVE

Prevent exposure of occupants to concentrated indoor sources of

pollutants.

C

REDIT ATTAINABLE

1

C

REDIT REQUIREMENT

1 credit for the provision of independent exhaust system for all

photocopy / printing rooms and locations where significant indoor

pollution sources are generated.

A

SSESSMENT

Criteria

The Applicant shall provide independent exhaust to all photocopy /

printing rooms and locations with significant indoor pollution sources

with sufficient exhaust rate. On the other hand, the Applicant shall

ensure the discharge of the exhaust louvres shall not face or at a

minimum distance of 7m to other intake location points or louvres.

Documentation

Credit shall be achieved when the Applicant provides the

documentation stated below, to demonstrate criteria compliance:

i.

drawings, with location layout, sections, elevations for each

rooms, including E&M layout drawings, and associated

ductwork layouts;

ii.

fan schedules;

iii.

calculation that exhaust rate of 2.5 litres per second/sqm is

achieved;

iv.

commissioning records;

v.

record photographs;

NOTE: Record photographs shall be required during the progress of

the works for installations and systems that will be subsequently

covered up or concealed;

B

ACKGROUND

Concentrated airborne contaminants are best removed close to their

sources. The provision of independent exhaust, segregated from

general ventilation, is an appropriate strategy.

Photocopiers and printers emit contaminants such as ozone and

particulates and should be housed in dedicated rooms that are not

normally occupied.

ANSI/ASHRAE 62.1-2010

[1

] designates the air quality in copy and

print rooms as air class 2 and it is therefore inappropriate to re-

circulate with occupied areas of the building. ANSI/ASHRAE 62.1-

2010 recommends an exhaust flow rate of 2.5 l/s/m

2

.

1

ANSI/ASHRAE 62.1-2010. Ventilation for Acceptable Indoor Air Quality. American Society of Heating, Refrigerating

and Air-Conditioning Engineers, Inc.